Contents
Cover
Title Page
Copyright
About the Authors
Preface to the Fourth Edition
Acknowledgements
Chapter 1: Introduction
1.1 Layout of Chapters
1.2 Wiring Regulations
1.3 Terminology
1.4 Competence and Responsibility
1.5 Procedures
1.6 Inspection and Test
1.7 Completion
1.8 Working Methods and Materials
1.9 Operatives
1.10 Materials
1.11 Amendments to BS 7671: 2008
1.12 Voltages
1.13 Voltage Drop
Chapter 2: Three Bedroom House
2.1 The Bare Minimum
2.2 Standards
2.3 Building Regulations
2.4 Load Assessment
2.5 A Typical Domestic Supply
2.6 Project Specification
2.7 Wiring Systems and Cable Sizes
2.8 Lighting
2.9 13 A Socket-Outlets
2.10 Cable Sizes
2.11 Circuit Protection
2.12 Additional Protection for Socket-Outlets
2.13 Arrangement of Circuits
2.14 Arrangement of Consumer Unit
2.15 Main Switch
2.16 Earthing and Bonding
2.17 Gas Services Bonding and External Meters
2.18 Supplementary Bonding
Chapter 3: A Block of Retirement Flatlets
3.1 Two Schemes
3.2 Early Considerations
3.3 Other Interested Parties
3.4 Building Details
3.5 Part 1 – Flats
3.6 Part 2 – Landlord's Areas
Chapter 4: Overcurrent Protection
4.1 Overload
4.2 Overload Protection
4.3 Overload Protective Devices
4.4 Fault Current
4.5 Fault Current Protection
4.6 Omission of Fault Current Protection
4.7 Short-Circuit Rating
4.8 Disconnection Times
4.9 Earth Loop Impedance
4.10 Summary of cb Specification
4.11 Conclusion
Chapter 5: An Architect's Office
5.1 Other Interested Parties
5.2 Building Structure and Finishes
5.3 Electrical Requirements
5.4 Skirting System
5.5 Underfloor System
5.6 Socket-Outlets
5.7 Lighting Circuits
5.8 Battened Out Ceilings
5.9 Extra-Low Voltage Lighting (elv)
5.10 Group Transformers
5.11 Individual Transformers
5.12 Fire Prevention
5.13 Arrangement of Circuits
5.14 Distribution Boards
5.15 Cable Sizes
5.16 Switchgear
5.17 Print Machine
5.18 Wall Heaters in Toilets
5.19 Storage Heaters
5.20 Presence of 400 Volts
5.21 Access to Switchgear
5.22 Earthing and Bonding
5.23 Main Earthing Terminal
5.24 False Ceiling Grid
5.25 Computer Installations
5.26 High Protective Conductor Currents
5.27 Mains Filters
5.28 Uninterruptible Power Supplies (UPS)
Chapter 6: A High Street Shop
6.1 Special Considerations
6.2 Other Interested Parties
6.3 Building Structure and Finishes
6.4 Electrical Requirements
6.5 Loading and Diversity
6.6 Lighting
6.7 Socket-Outlets
6.8 Other Appliances
6.9 Phase Balance
6.10 Wiring Systems
6.11 Start by Considering Cost
6.12 Shop Area
6.13 Bakery Area
6.14 Temperature Limit of 70 °C
6.15 Temperature Limit of 90 °C
6.16 Final Selection and Cable Sizes
6.17 Bakery Wiring
6.18 Shop Wiring
6.19 Distribution Board
6.20 Cable Sizes
6.21 Switchgear
6.22 Isolation and Switching
6.23 Earthing and Bonding
6.24 Main Earthing Terminal (MET)
6.25 False-Ceiling Grid
6.26 Steel Tables in the Bakery
Chapter 7: Earthing and Bonding
7.1 Terminology
7.2 Definitions
7.3 Green-and-Yellow Conductors
7.4 Protective Earthing and Protective Equipotential Bonding
7.5 Protective Multiple Earthing (PME)
7.6 Reliability of the Earth-Neutral Path
7.7 Main Bonding
7.8 Single Fault Condition
7.9 Supplementary Bonding
7.10 Circuit Protective Conductors (CPCs)
7.11 Steel Conduit and Trunking
7.12 Steel Wire Armoured Cable
7.13 Comparison of Thermoplastic (PVC) and Thermosetting (XLPE) Armoured Cable
7.14 Continuity of Cable Glands
7.15 Equipment Having High Protective Conductor Currents
7.16 Protective Conductor Currents
7.17 ‘High Integrity’ Earthing
7.18 Earth Monitoring and Isolated Supplies
7.19 Socket-Outlets for Desktop Computers
7.20 Connections of Protective Conductors
7.21 Residual Current Devices
Chapter 8: Car Service Workshop
8.1 Standards and Recommendations
8.2 An Adaptable Design
8.3 Motor Vehicle Repair Premises
8.4 Other Interested Parties
8.5 Building Structure and Finishes
8.6 Construction
8.7 Electrical Requirements
8.8 Health and Safety Executive Guidance and Regulations
8.9 Health and Safety Guidance Note HSG 261
8.10 Wiring Regulations
8.11 Load Assessment and Maximum Demand
8.12 Maximum Demand Load and Diversity
8.13 Lighting
8.14 Welder
8.15 Compressor
8.16 Gas Blowers
8.17 Phase Balance
8.18 Estimate of Maximum Demand
8.19 What about a Distribution Circuit (Sub-Main)?
8.20 Wiring Systems
8.21 Workshop
8.22 Office
8.23 Arrangement of Circuits
8.24 Distribution Boards
8.25 Cable Sizes
8.26 Isolation and Switching
8.27 Machinery
8.28 Cooker
8.29 Gas Boiler
8.30 110 V Transformer
8.31 Earthing and Bonding
8.32 Main Earthing Terminal
8.33 Protective Conductors at Distribution Board B
8.34 Armoured Cable Glands
8.35 Steel Conduit and Trunking
Chapter 9: Circuits
9.1 Terminology
9.2 Colours of Three Phases
9.3 Conventional Circuits
9.4 Lighting Circuits
9.5 Induction
9.6 Socket-Outlet Circuits
9.7 Changing Methods
9.8 Ring Main Obsolescence
9.9 History of the Ring Final Circuit
9.10 Times have Changed
9.11 Alternative Methods
9.12 Radial Circuits
9.13 Introducing the Tree
9.14 20 A Tree
9.15 32 A Tree
9.16 Switching and Control
9.17 Comparison of Systems
9.18 32 A Ring Final Circuit
9.19 20 A Tree
9.20 Composite Circuits
Chapter 10: Farming and Horticulture
10.1 Why Farms are Different
10.2 Special Earthing Requirements on Farms with TT Systems
10.3 Earth Electrodes
10.4 Alternative Electrodes
10.5 Bonding
10.6 Supplementary Bonding
10.7 Residual Current Devices
10.8 Shock Protection
10.9 General Requirements for Automatic Disconnection of Supply (ADS)
10.10 Fire Protection
10.11 Automatic Life Support for High Density Livestock Rearing
10.12 Switchgear
10.13 Wiring Systems
10.14 Overhead or Underground Wiring
10.15 Non-Metallic Wiring Systems
10.16 Steel Wire Armoured (SWA) Cable
10.17 Twin and Earth Cable
10.18 General Rules Regarding Farm Electrical Installations
Chapter 11: Isolation and Switching
11.1 Isolation and Switching
11.2 Isolation
11.3 Mechanical Maintenance
11.4 Emergency Switching
11.5 Labelling and Notices
Chapter 12: A Village Sports Centre
12.1 Special Conditions
12.2 Codes of Practice
12.3 Other Interested Parties
12.4 Building Details
12.5 Structure and Finishes
12.6 Electricity Supply and Requirements
12.7 Off-Peak Tariff
12.8 Normal Tariff
12.9 Load Assessment and Diversity
12.10 Off-Peak Heating
12.11 Normal Tariff
12.12 Total Estimated Maximum Current Demand
12.13 Wiring Systems
12.14 Circuitry and Cable Sizing
12.15 Cable Grouping Factors
12.16 Arrangement of Circuits
12.17 Switchgear
12.18 Shock Protection
12.19 Earthing
12.20 Bonding
12.21 An Occasional Problem
12.22 Solutions
12.23 Requirements for a TT Installation
Chapter 13: An Indoor Swimming Pool
13.1 Special Conditions
13.2 Other Interested Parties
13.3 Building Details
13.4 Application of Zoning to this Project
13.5 Dehumidifiers
13.6 Changing Room/Shower Area
13.7 Loading and Diversity for the Swimming Pool Project
13.8 Wiring Systems
13.9 Cable Sizes
13.10 Distribution Board
13.11 Isolation
13.12 110 V System
13.13 Earthing
13.14 Local Supplementary Bonding
13.15 Floor Grid
Chapter 14: Cables and Wiring Systems
14.1 External Influences
14.2 Cost Considerations
14.3 Choosing Suitable Cable Routes
14.4 Is Armouring Always Necessary?
14.5 Fire Barriers
14.6 Holes through Fire Barriers
14.7 Sealing the Wiring System
14.8 Work in Progress
14.9 Records
14.10 Hidden Cables
14.11 Cables within a Floor
14.12 Cables above False Ceilings
14.13 Cables in Walls
14.14 Mechanically Protected Cables
14.15 Fire and Smoke
14.16 Thermoplastic (PVC) Insulation
14.17 Thermosetting (XLPE)
14.18 Silicone Rubber
14.19 Low Smoke Zero Halogen (LS0H)
14.20 Mineral Insulated Copper Sheathed (MICS) Cables
14.21 Heat Transference from Cables
14.22 Wiring Systems and Cable Management
14.23 Emergency Systems
14.24 Care with Wiring Systems
14.25 Thermoplastic (PVC) Insulated and Sheathed Cables
14.26 Thermosetting (PVC) Insulated Conduit Cables
14.27 Steel Conduit Systems and Trunking
14.28 Plastic Conduit Systems and Trunking
14.29 MICS Cables
14.30 Steel Wire Armoured Cables
14.31 Silicone Insulated PVC Sheathed Cables
Chapter 15: Inspection, Testing and Certification
15.1 Labelling and Documentation
15.2 Specification and Manual
15.3 Regulations
15.4 Electrical Installation Certificate (EIC)
15.5 Signatories
15.6 Alterations and Additions
15.7 Limits of Responsibility
15.8 Deviations and Departures
15.9 New Materials and Inventions
15.10 Particulars of the Installation
15.11 Inspections and Test Schedules
15.12 Inspection Procedures
15.13 Testing
15.14 Continuity Testing
15.15 Polarity
15.16 Continuity of Protective Conductors
15.17 Continuity of Ring Circuit Conductors
15.18 Insulation Resistance
15.19 Earth Fault Loop Impedance
15.20 Supply Impedance Ze
15.21 Earth Loop Impedance of Circuits Zs
15.22 Prospective Fault Current
15.23 Operation of Residual Current Devices
Chapter 16: A Caravan Park
16.1 Measures for Protection against Electric Shock
16.2 Earthing Arrangements
16.3 PME Must Not be Used for Caravans
16.4 Electrical Equipment (External Influences)
16.5 Wiring Systems
16.6 Cables Buried in the Ground
16.7 Overhead Cables
16.8 Caravan Pitch Electrical Supply Equipment
16.9 Plugs and Socket-Outlets
Chapter 17: Residual Current Devices
17.1 How does an RCD Work?
17.2 Fault Protection
17.3 Additional Protection
17.4 Requirements to Provide Additional Protection by RCDs
17.5 RCDs Incorporated Into a Consumer Unit, to Meet the Requirements for Additional Protection
17.6 Protection against Fire
17.7 Avoiding a Hazard and/or Minimising an Inconvenience due to the Tripping of an RCD
17.8 Reducing the Possibility of Unwanted Tripping of RCDs
17.9 Use of a ‘Front-End’ 30 mA RCD is Generally Considered Unacceptable Practice
17.10 Installations Forming Part of a TT System
17.11 RCDs Connected in Series
17.12 Labelling
Chapter 18: Flood Lighting (Outdoor Lighting) Project
18.1 Lighting Arrangement
18.2 General Requirements
18.3 Wiring System
18.4 Protective Measures
18.5 Load Assessment
18.6 Rating of the Overcurrent Protective Device
18.7 Circuit Design
18.8 Voltage Drop Consideration
18.9 Switchgear
Chapter 19: Circuit Design Calculations
19.1 Design Process
19.2 Protective Conductors
19.3 Worked Example
19.4 Solution
Index
This edition first published 2013
© 2013, John Wiley & Sons, Ltd
Registered office
John Wiley & Sons Ltd, The Atrium, Southern Gate, Chichester, West Sussex, PO19 8SQ, United Kingdom
For details of our global editorial offices, for customer services and for information about how to apply for permission to reuse the copyright material in this book please see our website at www.wiley.com.
The right of the author to be identified as the author of this work has been asserted in accordance with the Copyright, Designs and Patents Act 1988.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, except as permitted by the UK Copyright, Designs and Patents Act 1988, without the prior permission of the publisher.
Wiley also publishes its books in a variety of electronic formats. Some content that appears in print may not be available in electronic books.
Designations used by companies to distinguish their products are often claimed as trademarks. All brand names and product names used in this book are trade names, service marks, trademarks or registered trademarks of their respective owners. The publisher is not associated with any product or vendor mentioned in this book. This publication is designed to provide accurate and authoritative information in regard to the subject matter covered. It is sold on the understanding that the publisher is not engaged in rendering professional services. If professional advice or other expert assistance is required, the services of a competent professional should be sought.
Library of Congress Cataloging-in-Publication Data
Electrical installation designs / Bill Atkinson ... [et al.]. – 4th ed.
p. cm.
Includes bibliographical references and index.
ISBN 978-1-119-99284-4 (pbk.)
1. Electric wiring, Interior. 2. Electrical engineering. I. Atkinson, Bill.
TK3271.A8 2013
621.319′24–dc23
2012030909
A catalogue record for this book is available from the British Library.
ISBN: 978-1-119-99284-4
Preface to the Fourth Edition
There are many books on electrical installation practice where the focus is on calculations and regulations. Electrical Installation Designs has been written from a different viewpoint. Typical projects are examined to produce designs that will fit current standards.
Most electrical contractors have an understanding of requirements related to their own regular everyday activities, where work is carried out using rule-of-thumb methods. Repetitive designs are used. Many installers claim that they are not designers and show concern that they are now required to certify the adequacy of an installation design.
In practice, problems only arise when an unusual project is undertaken or there is a change in regulations.
There is no harm in using a standardised design, rather in the way that an experienced cook uses a published recipe for a cake. Electrical Installation Designs is a book of recipes. The installer may select a design that corresponds as near as possible to the contract in hand and take up such technical and regulatory advice as is required. This will reduce the need for lengthy calculations and detailed study of BS 7671, Requirements for Electrical Installations (IET Wiring Regulations).
Most basic electrical installations may be completed by a competent person, with appropriate guidance to avoid serious problems and hazards.
Project chapters illustrate methods that could be used for particular types of installation ranging from a house to an industrial workshop. The ideas are by no means exclusive. Alternative solutions are always possible. In many instances carrying out detailed calculations and utilising different circuitry will be more profitable. By their very nature, simplified examples of fictional projects can only produce generalised results.
The book contains special chapters on earthing, isolation and switching and overcurrent protection, which give a down to earth interpretation of the regulations.
Electrical installation students and non-electrical associates in the construction industry will appreciate the user-friendly approach. Nevertheless, this is not a do-it-yourself book for the untrained person. Warnings are therefore given where more specialised study is necessary. For example, readers are advised not to embark on installations in hazardous areas (such as petrol filling stations) without further training. Apart from moral implications and contractual risks, statutory requirements are such that incompetent work may carry criminal penalties.
Although the emphasis is on tried and tested methods, some new techniques are introduced. The most significant is the option for tree circuitry as an alternative to the ring final circuit. This is the first book to give designers the opportunity to compare the advantages of the tree system for both domestic and commercial installations. In recent years, consumer requirements have changed. It is essential that the industry keeps an open mind on changes in traditional wiring practice. Introduced in this fourth edition are new chapters on Residual Current Devices and, for those readers who require a basic understanding of circuit design, a chapter explaining the process for carrying out simple cable design calculations.
Amendments
The Institution of Electrical Engineers (IEE) joint wiring regulations committee amended BS 7671: 1992 (16th edition) in 1994, 1997 and 1999. In 2001, the standard was renamed BS 7671: 2001 with further amendments, and minor amendments were made again in 2002.
In 2008, a complete review of the 16th edition saw the publication of the 17th edition: BS 7671: 2008. The first amendment to the 17th edition was published in 2011 and came fully into force on 1 January 2012. This latest amendment also introduced the rebranded name of the IEE, namely the IET (Institution of Engineering and Technology). The most recent edition of BS 7671 incorporates all alterations and additions to the European HD 384 series of standards.
As is often the case, many of the changes are of a minor nature in order to harmonise with other standards. However, significant changes were introduced in BS 7671: 2008 (17th edition) with several other significant changes being introduced in its first amendment, in 2011. These are summarised in the following tables – Table A.1 summarises the changes introduced by BS 7671: 2008 (17th edition) and Table A.2 summarises the significant changes introduced by Amendment 1 to BS 7671: 2008:
Table A.1 Summary of changes introduced by BS 7671: 2008 (17th edition).
General |
Regulation numbering system |
The 17th edition introduced the adoption of the IEC numbering system, in which the Regulation numbers are separated by a decimal point, rather than a hyphen as was previously the case. |
Chapter 41 |
Protection against electric shock |
Chapter was rewritten.
Protection against direct contact – was replaced by basic protection.
Protection against indirect contact – was replaced by fault protection.
Introduction of term ‘Additional protection’. Socket-outlets with a rated current not exceeding 20 A and intended for general use by ordinary persons must be protected by 30 mA RCDs.
Mobile equipment having a current rating of 32 A or less for use outdoors must also have 30 mA RCD protection. |
Chapter 52 |
Selection and erection of wiring systems |
For installations not under the supervision of a skilled or instructed person, such as domestic or similar installations, cables that are buried in a wall or partition at a depth of 50 mm or less and are not enclosed in earthed metallic covering (metallic armouring), earthed conduit, earthed trunking or have mechanical protection capable of resisting nails, screws or the like, are required to be protected by a 30 mA RCD as well as being installed in the so-called ‘safe zones’.
Similarly cables that are installed in metal framed walls require 30 mA RCD protection if not otherwise protected by earthed metallic covering, earthed conduit, earthed trunking or have mechanical protection capable of resisting nails, screws or the like, to be protected by a 30 mA RCD, unless the installation is under the control of skilled or instructed persons, such as office buildings and industrial premises. |
Section 559 |
Luminaires and lighting |
A new section applicable to all general lighting installations as appropriate to particular locations and structures. Requirements for fixed outdoor lighting, highway power supplies and street furniture are also included, which were previously in Part 6. |
Part 6 |
Inspection and testing |
Was previously Part 7. |
Part 7 |
Special installations or locations |
Was previously Part 6.
701 – Locations containing a bath or a shower.
Zones 0, 1 and 2 as defined in the 16th edition were retained. Zone 3 was removed. All circuits supplying equipment in bathrooms and shower rooms are required to be protected by 30 mA RCDs.
Supplementary bonding is no longer required, provided all of the following three conditions are met:
• all final circuits of the location are protected by a 30 mA RCD;
• all final circuits of the location meet the required disconnection times;
• main bonding of services within the property is correctly installed. |
|
|
SELV (separated extra-low voltage) socket-outlets and shaver socket-outlets are permitted outside Zone 1
230 V socket-outlets are permitted, provided they are more than 3 metres horizontally from the boundary of zone 1.
708 – Electrical installations in caravan/camping parks and similar locations. Formerly caravans, motor caravans and caravan parks in the 16th edition. |
|
|
New Sections were added as follows:
709 – Marinas and similar locations;
711 – Exhibitions, shows and stands;
712 – Solar photovoltaic (PV) power supply systems;
717 – Mobile or transportable units;
721 – Electrical installations in caravans and motor caravans;
740 – Temporary electrical installations for structures, amusement devices and booths at fairgrounds, amusement parks and circuses. |
Table A.2 Summary of changes introduced by Amendment 1 to BS 7671: 2008.
General |
Regulation numbering system |
In order to further implement changes to the requirements given in the International (IEC) and European (CENELEC) base documents, a number of the requirements contained in BS 7671 are particular to the United Kingdom. Those Regulations are identified via a ‘10X’ suffix. For example, Regulation 522.6.100. |
General |
References to ESQCR 2002 |
Amendments have been made throughout BS 7671 to clarify the requirements of the Electricity Safety, Quality and Continuity Regulations 2002 with regard to the suitability for use of Protective Multiple Earthing (PME). |
Tables 41.2; 41.4; and 41.6 |
BS 88 fuses |
Amended to reflect changes in product standards for cartridge fuses. |
Table 41.5 |
Simplification of table |
Scope of the table revised to cover only circuits at a nominal a.c. rms line-to-earth voltage (U0) of 230 V. |
Section 444 |
Measures against electromagnetic disturbances |
New section added, Measures against electromagnetic disturbances. |
514.10.1 |
Nominal voltages |
Simplification of wording regarding enclosures within which nominal voltages exceeding 230 V to earth are present but may not be expected.
Requirement relating to nominal voltage exceeding 230 V between simultaneously accessible enclosures has been deleted. |
522.6.100 |
Cables in floor or ceiling voids |
Clarification provided by adding indent relating to SELV and PELV circuits. |
522.6.101 |
Cables in walls or partitions |
Clarification provided by adding indent relating to SELV and PELV circuits. |
522.6.103 |
Cables in partitions having metallic parts |
Clarification provided by adding indent relating to SELV and PELV circuits. |
526.3 |
Connections |
Maintenance-free accessories complying with BS 5733 recognised as an option for not needing to be accessible for inspection and maintenance. |
Section 534 |
Surge protection devices |
New section added, Devices for protection against overvoltage. |
Section 710 |
Medical locations |
New section added, Medical locations. |
Section 729 |
Operating and maintenance gangways |
New section added, Operating and maintenance gangways. |
Appendix 4 |
Current-carrying capacity and voltage drop for cables |
New clauses added: 5.5, Rating factors for triple harmonic currents in four-core and five-core cables with four cores carrying current and 5.6 Harmonic currents in line conductors. (New clauses based on text that was previously in Appendix 11). |
|
|
New clause added: 6.4, Voltage drop in consumers' installations. (Text was previously in Appendix 12). |
Appendix 6 |
Model forms for certification and reporting |
Introduction of Electrical Installation Condition Report to replace Periodic Inspection Report.
New Schedule added: Condition report inspection schedule for domestic and similar premises with up to 100 A supply.
New item added for other types of installation: Examples of items requiring inspection for an electrical installation condition report. |
Appendix 16 |
Protection against overvoltage |
New Appendix added: Devices for protection against overvoltage. |
This book takes account of all amendments published since the 17th edition of the Wiring Regulations was first issued in 2008, including those introduced by Amendment 1, which was first issued in 2011 and which came into effect on 1 January 2012.
Roger Lovegrove and Gary Gundry
1
Introduction
This book contains designs for electrical installations that have been prepared with reference to the Wiring Regulations and includes interpretations of particular technicalities.
This is not a do-it-yourself book for the amateur or untrained person. It is a guidance manual for competent electrical designers and students of installation practice.
As far as possible, all information accords with the requirements of BS 7671: 2008, incorporating Amendment 1, 2011 Requirements for Electrical Installations, the IET Wiring Regulations (17th edition), which is issued jointly by the British Standards Institution (BSI) and the Institution of Engineering and Technology (IET) as BS 7671. Relevant Regulation numbers and other references are shown in the margins. (Because of the space restrictions, the following abbreviations have been used: Ch. – Chapter; Sec. – Section; Defs – Definitions; App. – Appendix.) Reference is also made to various other British and European Standards and related Health and Safety documentation.
1.1 Layout of Chapters
Interspersed throughout the book are two types of chapters, giving information in different formats.
1. Project chapters: These may be compared with a selection of recipes for an experienced chef. The recipes give ideas for the design of typical electrical installations. Each project is dealt with on a stand-alone basis. Cross-references between these chapters are avoided, wherever possible, and similar information may be found for more than one scheme.
2. Topic chapters: These supplement the project chapters with in-depth discussion of generalised technicalities. They also provide study information on regulatory subjects. It may be necessary to refer to these details to finalise a design with particular problems.
1.2 Wiring Regulations
Throughout this book the terms Wiring Regulations (or Regulations) refer to BS 7671:2008 Requirements for Electrical Installations, the IET Wiring Regulations, issued jointly by the BSI and the IET. The Standard therefore represents a code of acceptable safety for electrical installations to protect:
131.1
- persons;
- property; and
- livestock.
against electrical hazards, which are described as:
- electric shock;
- fire;
- burns;
- ignition of a potentially explosive atmosphere;
- undervoltages, overvoltages and electromagnetic effects;
- injury from mechanical movement of electrically actuated machinery;
- power supply interruptions or interruptions of safety services; and
- arcing or burning, excessive pressure or toxic gases.
114.1
The Regulations are not a statutory document, but are quoted as a means of compliance with certain statutory instruments. Criminal charges could not be brought for failure to comply with the Wiring Regulations, and such non-compliance could be used in evidence if there were a charge for breach of the forthcoming Electrical Safety Quality and Continuity Regulations (ESQCR) or the Electricity at Work Regulations.
It would be most unwise to ignore any of the requirements of the Regulations. They must be considered in their entirety and are a pass or fail test. An installation cannot partially comply.
1.3 Terminology
In order to understand technicalities, the importance of correct terminology is stressed throughout this book. In general, however, the use of overcomplicated expressions and trade jargon has been avoided.
The Wiring Regulations contain a list of definitions for words and expressions, which may not accord with standard dictionary definitions. Wherever there is any doubt, the Wiring Regulations definition should be applied.
1.4 Competence and Responsibility
Any person involved with the installation of wiring in buildings takes on both legal and moral responsibilities for safety. A high level of technical and practical competence is essential. This can only be achieved with appropriate study.
There are always three components to an electrical installation project:
1. Design;
2. Installation;
3. Inspection and testing.
Often one person or company takes on all three responsibilities, especially for simple repetitive jobs such as house wiring. On larger schemes, specialist companies may be contractually involved for each aspect and in turn use a team of operators. As the work progresses from planning to completion, there must always be one or more supervising individuals, who will eventually certify that the three aspects of the contract have been carried out in accordance with the Wiring Regulations and any other statutory or specification requirements.
1.5 Procedures
1.5.1 Design
It is sometimes thought that the use of tried and tested methods removes the design aspect from a scheme. This is not the case. Every project involves electrotechnical design decisions, which should not to be confused with architectural or customer instructions for the physical location of electrical equipment. Thus, a self-employed electrical contractor, who makes a decision on the selection and connection of an electrical accessory, is a designer. The same applies to an electrician who makes a similar decision on behalf of an employer.
514.9
All technical design information must be recorded. This is a requirement of the Wiring Regulations. IET guidance stresses that it is essential to prepare a full specification prior to commencement or alteration of an electrical installation. The size and content of the specification will correspond with the complexity of the work. For simple installations, a schedule of circuit details and test results may suffice.
The designs shown in the following chapters are for guidance only and each one includes a suggestion for a suitable design specification. A person selecting this guidance makes a design decision and therefore becomes the person responsible.
632.3
Upon completion of a contract, the person or persons responsible for the design, construction, and inspection and testing of the installation must, as appropriate, provide the person who ordered the work with an Electrical Installation Certificate, stating the works that were carried out, together with schedules for inspection and for test results.
1.5.2 Installation
Where a technical design is drawn up by an electrical engineer or other competent person, it should not be the installer's job to check design details, unless this is one of the contract requirements. The installer is always under obligation to point out to the designer any obvious conflict with regulations or standards and the installer should always refuse to carry out substandard work. There would be no defence in law against creating an unsafe installation on the basis of inherently bad instructions.
The installer will use the designer's specification document as required by the Wiring Regulations. This may only cover performance requirements or may give full technical details for the selection and erection of equipment. Once again it must be emphasised that a non-technical instruction to take an electrical supply to a particular appliance or location does not constitute design information.
The installer has the responsibility to ensure that equipment is installed correctly and in accordance with the specification, supplemented by manufacturers' information. The installer is often delegated other tasks, such as that of negotiating with the electricity supply company and verifying local licensing requirements.
Upon completion of the project, the installer certifies that the installation work has been carried out in accordance with the Wiring Regulations.
1.6 Inspection and Test
610.1
No matter how simple or straightforward a job is, the work should always be inspected, both during the course of the work, and upon completion, and tested before the installation is put into service. This applies equally to work carried out by a self-employed operator. Self-certification is normally acceptable, provided that the contractor has the competence and equipment to test correctly. The customer or an insurer may require specialist certification. This particularly applies in the case of safety alarm systems or work in hazardous areas.
Whether an in-house or independent specialist, the inspector must be given the full design documentation, with amendments showing any relevant on-site modifications. On larger projects, this will include ‘as fitted’ drawings.
Certain parts of the installation may be hidden from view upon completion. In such cases the inspector must arrange for inspection during the course of erection or receive certified confirmation that the work is satisfactory.
631.1
Upon completion of the project, the inspector certifies that the inspection and test have been carried out in accordance with the Wiring Regulations.
1.7 Completion
632.3
The signatures of the designer, installer and inspector are required for the Electrical Installation Certificate. This cannot be issued until the work has been completed in accordance with the Wiring Regulations. Where there are acceptable departures from the Regulations, these must be shown on the certificate. See Chapter 15 for inspection and test procedures.
1.8 Working Methods and Materials
134.1.1
The Wiring Regulations require good workmanship by competent persons and that proper materials are used.
1.9 Operatives
Any person carrying out electrical work must be competent, trained and skilled in the type of installation work being carried out. Where trainees or unskilled operatives are employed for electrical work, they must be appropriately supervised.
Workmanship must be of a quality appropriate to the location. A working knowledge of the building structure is necessary where holes and fixings are made to carry cables. Decor should be disturbed as little as possible, with prearranged responsibility for making good.
1.10 Materials
511.1
The Regulations require that every item of equipment complies with a British or harmonised Standard. Alternatively, equipment complying with a relevant foreign standard may be used, provided that the designer confirms that the equipment provides a degree of safety acceptable to the Regulations. This may mean product certification by an approvals organisation.
1.11 Amendments to BS 7671: 2008
There is one amendment to BS 7671: 2008, published in 2011. Many of the changes are minor, resulting from European harmonisation, and the numbering of product standards where these have also been harmonised. Where changes have been made that affect the technical or practical aspects of this book, the text has been changed accordingly. If an amendment noticeably alters conventional procedures, details of the change have been included. This particularly applies in the case of voltage harmonisation.
1.12 Voltages
On 1 January 1995, the Electricity Supply Regulations 1988 were changed to take into account a change in the standard UK supply voltage (Table 1.1). All specifications, designs and calculations should now use the 230/400 V figures. The change in voltage is minimal, therefore load assessments given in this book have not been recalculated, but there are other consequences to be considered.
Table 1.1 Changes in nominal voltage.

Taking all of the above factors and tolerances into account, it will be seen that under the most extreme circumstances, equipment rated at 230 V may be supplied at anything between 216 and 253 V.
1.13 Voltage Drop
The Regulations require the voltage at the terminals of fixed current-using equipment under normal service conditions to be greater than the lower limit corresponding to the product standard for that equipment.
For an installation supplied from a public supply, a voltage drop of 3% for lighting and 5% for other uses is deemed to satisfy this requirement. At 230 V, this is 6.9 V and 11.5 V, respectively. Care therefore needs to be taken in the selection of cables, particularly where equipment is voltage-dependent:
- Motor starting currents may be such that machines may stall before achieving full speed running conditions.
- Inductive lighting loads take high current on start up and luminaires could fail to strike, especially in cold weather.
All of the designs shown in this book use cables that are capable of handling the prospective loadings with a reasonable margin of safety.